What It Means
Circuit A condensing temperature sensor out of range.
Troubleshooting guide for the Carrier Packaged Unit system fault 64.
Circuit A condensing temperature sensor out of range.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Condensing Temperature Failure - Circuit A. Condensing temperature is outside the valid range and fans are controlled from outdoor temperature.
Check circuit A condensing temperature sensor wiring and connector. Measure sensor resistance against temperature/resistance chart. Inspect for refrigerant overcharge causing high condensing temperature. Replace sensor if out of spec.