What It Means
Freeze (anti-frost) protection has tripped on the fan coil's water coil.
Troubleshooting guide for the Daikin Fan Coil system fault A4.
Freeze (anti-frost) protection has tripped on the fan coil's water coil.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Freeze (anti-frost) protection has tripped on the fan coil's water coil. Unlike Daikin's refrigerant-circuit indoor units, a fan coil has no compressor or expansion valve — cooling and heating are supplied entirely by chilled or hot water circulated through the coil, and the fan simply moves indoor air across it. When the coil's water temperature drops low enough to risk ice forming on the fins, the controller closes the modulating water valve (or breaks the circulating-pump interlock) and stops the fan to protect the coil from splitting. Unlike A3 (drain level fault, a condensate-handling issue), A4 is a water-side temperature protection fault tied directly to the hydronic loop, not the drain pan.
Insufficient chilled/hot water flow through the coil (partially closed isolation or balancing valve, air-locked coil, undersized circulator, clogged strainer) Water temperature setpoint at the plant/chiller set too low for the coil design, or a sequencing fault delivering water colder than the coil can tolerate Defective or drifted water temperature thermistor giving a false low reading Loose or corroded thermistor connector Control valve stuck partially closed, starving the coil of flow