What It Means
Pressure switch failed to close or reopened during operation.
Troubleshooting guide for the Bryant Furnace system fault 31.
Pressure switch failed to close or reopened during operation.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Pressure Switch Did Not Close or Reopened. If open longer than 5 minutes, inducer shuts off for 15 minutes before retry. Check venting, inducer, switch, tubing, combustion air, wind, and inlet gas pressure if LPGS is used.
Check inducer motor speed and operation. Inspect pressure switch tubing for blockage or leaks. Test pressure switch with manometer. Verify vent system is clear and properly sized. Check inlet gas pressure if using LP gas.