What It Means
Incoming line voltage dropped below 187 V for over 4 seconds.
Troubleshooting guide for the Carrier Air Conditioner system fault 46.
Incoming line voltage dropped below 187 V for over 4 seconds.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Brown Out (230 V). Line voltage is less than 187 V for at least 4 seconds; compressor and fan operation are not allowed until voltage exceeds 190 V.
Measure supply voltage at outdoor disconnect under load. Check for undersized wiring or loose connections. Contact utility company if supply voltage is consistently below spec.
ACLogics walks you through Carrier Air Conditioner diagnostics step-by-step — so you confirm the cause before swapping parts.