What It Means
Open or shorted ambient outdoor air temperature sensor circuit.
Troubleshooting guide for the Trane AC & Heat Pump system fault Red 5 Flashes.
Open or shorted ambient outdoor air temperature sensor circuit.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Ambient (outdoor air) temperature sensor fault — the control board is reading an open or shorted circuit from the sensor that measures outdoor air temperature, which the board uses for defrost timing and low-ambient cooling lockout. This is a separate circuit from Red 6 Flashes (the outdoor coil temperature sensor, used for defrost sensing) and Red 13 Flashes (an external/auxiliary outdoor sensor on some installations) — all three sensors report similar-looking faults but fail independently of one another.
Locate the ambient sensor (typically mounted at the outdoor unit's air inlet, separate from the coil sensor) and inspect its wiring and connector for corrosion, pinching, or looseness. If you can measure resistance, compare it against the temperature/resistance chart in the installation manual — a reading of zero (short) or infinite (open) confirms sensor failure. If the wiring and connector are intact but the fault persists, replace the ambient sensor; this is typically a low-cost part swap, not a control-board failure.
ACLogics has guided diagnostics for 36 Trane fault codes and asks the right questions to narrow it down.