What It Means
Indoor room temperature sensor T1 is open or short-circuited.
Troubleshooting guide for the Bryant Ductless Mini-Split system fault E4.
Indoor room temperature sensor T1 is open or short-circuited.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Indoor Room Temperature Sensor T1 Open or Short. Indoor room temperature sensor T1 is open-circuit or short-circuit.
Check T1 sensor wiring and connector for damage or corrosion. Measure sensor resistance and compare to temperature/resistance chart. Replace T1 sensor if resistance is outside specifications.
ACLogics walks you through Bryant Ductless Mini-Split diagnostics step-by-step — so you confirm the cause before swapping parts.