What It Means
Loss of communication between the CCM and the outdoor unit's Function Module.
Troubleshooting guide for the Luxaire system fault 02#.
Loss of communication between the CCM and the outdoor unit's Function Module.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Loss of communication between the CCM (Communicating Control Module) and the outdoor unit's Function Module — the auxiliary board that manages accessory functions like electric heat staging, humidity control, or zoning inputs. Unlike 00# (CCM-to-main PCB) or 01# (CCM-to-NIM) faults, this drop is isolated to the Function Module's data line, so core compressor and fan operation can often continue while the affected accessory functions are disabled. The board typically flashes this code and suspends Function Module–dependent features until communication is restored.
Inspect the communication wiring and connector between the CCM and the Function Module for loose pins, corrosion, or damage. Confirm the Function Module has power and, if equipped, that its status LED is lit. Check for a bus wiring short or open that affects only this module while 00#/01#/03# remain clear. Reseat or replace the Function Module if wiring tests good but the fault persists.