Full Diagnosis
J5 signals a fault in the thermistor monitoring suction (compressor inlet) gas temperature on the outdoor unit, which the controller relies on for superheat calculation and compressor protection logic; a bad reading here causes the affected outdoor module to shut down, since accurate suction temperature is essential to prevent liquid refrigerant floodback into the compressor. On a multi-module VRV system this is a single-module fault, isolating that outdoor unit while other modules continue running. Distinguish it from J6 (outdoor heat exchanger thermistor), J7 (main liquid pipe thermistor), and J9 (gas pipe thermistor) — J5 is specifically the suction-line sensor feeding compressor protection, not a heat-exchanger or liquid-line reading.
All Recorded Causes
Defective or drifted suction pipe thermistor, poor thermal contact between thermistor and pipe (loose clamp, missing insulation), broken or corroded thermistor wiring, damaged or disconnected connector at the outdoor unit PCB, defective outdoor unit control PCB input circuit.
Verify Before Replacing Parts
- Confirm the exact Daikin model family and vrv context before acting on a generic code description.
- Verify airflow first, then confirm operating pressures and temperature relationship before adjusting charge, since defective or drifted suction pipe thermistor, poor thermal contact between thermistor and….
- Look for restrictions, iced coils, or dirty heat-transfer surfaces that can mimic a charge problem, and separately confirm the next candidate on the list.
- After the correction, run the system long enough to confirm the vrv fault does not return under normal load.