What It Means
Reports a general fault in the outdoor/condenser fan motor circuit — most often the fan failing to start, rotate, or reach commanded speed, detected through motor current or feedback rather than a discrete overcurrent threshold.
Troubleshooting guide for the Daikin Chiller system fault E7.
Reports a general fault in the outdoor/condenser fan motor circuit — most often the fan failing to start, rotate, or reach commanded speed, detected through motor current or feedback rather than a discrete overcurrent threshold.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Reports a general fault in the outdoor/condenser fan motor circuit — most often the fan failing to start, rotate, or reach commanded speed, detected through motor current or feedback rather than a discrete overcurrent threshold. On this chiller, that differs from 72, which is a specific overcurrent trip on the System No. 2 fan circuit, and from H7, which reports a lost or corrupted feedback signal from the fan motor rather than the motor failing to run at all. Loss of condenser fan airflow will typically drive the affected circuit toward a high-pressure trip if not corrected.
Fan motor winding failure or seized bearing. Harness or connector between the fan motor and PCB disconnected or damaged. Foreign debris or ice blocking the fan blade. Failed run capacitor on single-phase fan motors, or a failed driver module on EC fans. Blown fuse or tripped breaker feeding the fan circuit.