What It Means
Indicates the inverter control PCB itself has detected an internal fault — commonly a blown fuse, a failed power module, or a wiring problem on the compressor or fan output side — and has shut down the inverter drive.
Troubleshooting guide for the Daikin Chiller system fault L1.
Indicates the inverter control PCB itself has detected an internal fault — commonly a blown fuse, a failed power module, or a wiring problem on the compressor or fan output side — and has shut down the inverter drive.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Indicates the inverter control PCB itself has detected an internal fault — commonly a blown fuse, a failed power module, or a wiring problem on the compressor or fan output side — and has shut down the inverter drive. This differs from L0, which reports a broader inverter system fault tied to insufficient power supply capacity, and from LC, which is specifically a lost communication link between the inverter PCB and the main control PCB rather than a fault on the inverter board itself. Because L1 can be triggered by downstream wiring as well as the board, verify compressor and fan output wiring before replacing the inverter PCB.
Blown fuse on the inverter PCB. Failed power module (IGBT/IPM) on the board. Damaged or shorted compressor output wiring. Damaged or shorted outdoor fan motor wiring. Loose or corroded connector at the inverter PCB. Moisture intrusion into the electrical component box.