What It Means
General transmission line communication failure between indoor and outdoor units.
Troubleshooting guide for the Mitsubishi Electric system fault EE.
General transmission line communication failure between indoor and outdoor units.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Error detail: this is a general indoor/outdoor communication fault raised when the transmission line between the indoor unit(s) and the outdoor unit loses signal integrity, distinct from the more granular E6/E7/E8/E9 codes that pinpoint whether the failure is on the indoor or outdoor side and whether it is a receiving or transmitting fault. Because the indoor and outdoor boards can no longer exchange operating data, the system halts normal operation and the outdoor unit drops compressor and fan output until communication is restored. EE typically points to a shared bus problem (wiring, connector, electrical noise) affecting the whole system rather than a single indoor unit's sensor, which would instead trigger a P-series thermistor code.
Loose, corroded, or reversed transmission line connections at the indoor or outdoor terminal blocks. Damaged, pinched, or water-intruded communication cable. Electrical noise from nearby high-voltage wiring or ungrounded equipment interfering with the signal. Address or wiring conflicts when multiple indoor units share one outdoor unit. Failed indoor or outdoor control board transmission circuit. Cable length or gauge exceeding manufacturer spec, degrading the signal.
ACLogics has guided diagnostics for 73 Mitsubishi Electric fault codes and asks the right questions to narrow it down.