What It Means
Outdoor board LED flash diagnostic for missing open power phase leg.
Troubleshooting guide for the Mitsubishi Electric system fault LED LD2 (Flash).
Outdoor board LED flash diagnostic for missing open power phase leg.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Diagnosis of malfunction: this LED flash pattern indicates the outdoor unit's phase-monitoring circuit has detected a missing (open) power leg on the incoming supply feeding the compressor, distinct from LD1, which flags a reversed phase sequence where all three legs are present but wired in the wrong rotational order. It is the LED-blink equivalent used on outdoor control boards without a digital display, corresponding to the same class of fault reported as F2 (L3 open phase) or FA (L2 open phase/51CM) on units read through a digital remote or service tool. Because a missing phase leg would cause the compressor to single-phase and overheat, the outdoor board locks out compressor and often fan operation immediately and holds the lockout until incoming power is restored to all legs.
Blown fuse or tripped breaker on one incoming phase leg. Loose, corroded, or disconnected terminal on the outdoor unit's main power block. Failed contactor with a contact not closing on one leg. Utility-side single-phasing or a downed/failed phase conductor. Damaged phase-monitoring relay or its wiring harness. Miswired or incomplete power disconnect installation.
ACLogics has guided diagnostics for 73 Mitsubishi Electric fault codes and asks the right questions to narrow it down.