What It Means
Abnormally low discharge superheat risking liquid refrigerant slugging.
Troubleshooting guide for the Mitsubishi Electric system fault U7.
Abnormally low discharge superheat risking liquid refrigerant slugging.
Not sure which one it is — or if it's none of these? Try ACLogics today.
Error detail: the outdoor unit's superheat control logic calculates discharge superheat from the discharge thermistor and finds it abnormally low, indicating the compressor may be running too close to saturation or drawing in liquid refrigerant rather than fully vaporized gas. The outdoor control board reduces or shuts down compressor operation to prevent liquid slugging and oil washout damage, then typically attempts a restart once conditions normalize but locks out after repeated occurrences. This differs from U3, which flags a hard-failed discharge thermistor (open/short circuit); U7 assumes the sensor is reading correctly but the underlying refrigerant condition is abnormal.
Refrigerant overcharge or undercharge. Expansion valve (LEV) stuck open or not modulating correctly. Low compressor load combined with excess liquid migration on startup. Faulty or drifting discharge thermistor calibration. Refrigerant migration during long off-cycles without crankcase heater operation. Restricted or undersized liquid line causing miscalculated flash gas. Mixed refrigerant charge or non-condensable gas in the system.