What It Means
Indoor unit T2A coil/pipe temperature sensor hardware fault.
Troubleshooting guide for the York system fault E3.
Indoor unit T2A coil/pipe temperature sensor hardware fault.
Not sure which one it is — or if it's none of these? Try ACLogics today.
E3 indicates the indoor unit's T2A temperature sensor — a coil/pipe sensor position distinct from T1 (reported under E2) and T3 (reported under E5) — is reading open, shorted, or outside its valid range. This is a physical sensor hardware fault, unlike E4, which reports a corrupted indoor EEPROM (stored configuration memory) rather than any temperature reading. When E3 trips, the indoor unit typically ends the active cycle and blocks compressor restart on that zone until the sensor input returns to normal, without affecting other indoor units on the same outdoor system.
Check the T2A sensor's wiring and connector at the indoor PCB for looseness, corrosion, or damage. Confirm the sensor is properly clipped to its coil or pipe location and making good contact. Test sensor resistance at a known temperature against the manufacturer's chart. Replace the sensor if it reads open, shorted, or inconsistent with actual coil temperature.