Full Diagnosis
F6 indicates abnormally high refrigerant pressure or an overcharged system, distinguished from E3 (mechanical high-pressure switch trip) in that F6 is derived from thermistor readings across the refrigerant circuit rather than a dedicated pressure switch actuation. The outdoor unit reduces or shuts down compressor operation to prevent overpressure damage. A common root cause is refrigerant overcharge from an improper service fill, though a disconnected sensing thermistor can produce a false high-pressure reading with the same symptom.
All Recorded Causes
Refrigerant system overcharged beyond rated capacity, disconnected or open-circuit heat exchanger deicer thermistor, disconnected or open-circuit outdoor air thermistor, disconnected or open-circuit liquid pipe temperature thermistor, restricted or undersized outdoor coil airflow, defective outdoor unit control PCB.
Verify Before Replacing Parts
- Confirm the exact Daikin model family and skyair context before acting on a generic code description.
- Verify airflow first, then confirm operating pressures and temperature relationship before adjusting charge, since refrigerant system overcharged beyond rated capacity, disconnected or open-circuit heat ex….
- Look for restrictions, iced coils, or dirty heat-transfer surfaces that can mimic a charge problem, and separately confirm the next candidate on the list.
- After the correction, run the system long enough to confirm the skyair fault does not return under normal load.