What It Means
P3 reports a malfunction of the thermistor located in the switch (electrical component) box — specifically the reactor thermistor that monitors temperature on the inverter's reactor component to prevent it from overheating.
Troubleshooting guide for the Daikin SkyAir system fault P3.
P3 reports a malfunction of the thermistor located in the switch (electrical component) box — specifically the reactor thermistor that monitors temperature on the inverter's reactor component to prevent it from overheating.
Not sure which one it is — or if it's none of these? Try ACLogics today.
P3 reports a malfunction of the thermistor located in the switch (electrical component) box — specifically the reactor thermistor that monitors temperature on the inverter's reactor component to prevent it from overheating. This is a sensor-circuit fault distinct from L3/L4, which report an actual electrical component box or radiation fin temperature rise event rather than a failure of the sensor reading it. The outdoor unit stops the inverter compressor as a precaution when this thermistor signal is lost or out of range.
Disconnected or loose reactor thermistor connector, open or shorted thermistor element, thermistor displaced from its mounting position on the reactor, defective inverter PCB sensor input circuit, wiring damage inside the switch box from heat or vibration.