Full Diagnosis
U5 reports a transmission failure specifically between the indoor unit and its wired remote controller, distinguishing it from U4, which covers indoor-to-outdoor unit communication loss, and from U8, which covers communication between two remote controllers on a dual-controller setup. Common triggers include two main (rather than one main and one sub) remote controllers wired to the same indoor unit, damaged control wiring, or electrical noise disrupting the signal. The affected zone stops responding to remote controller commands until communication is restored.
All Recorded Causes
Two main remote controllers wired to a single indoor unit instead of one main and one sub, damaged, pinched, or disconnected remote controller wiring, defective indoor unit PCB, defective remote controller PCB, electrical noise interference on the transmission line, incorrect remote controller address/mode setting.
Verify Before Replacing Parts
- Confirm the exact Daikin model family and skyair context before acting on a generic code description.
- Confirm board LEDs, wiring polarity, and model compatibility before replacing control boards — this Daikin fault points at two main remote controllers wired to a single indoor unit instead of one main and one sub,….
- Check for intermittent communication faults caused by connectors, moisture, or damaged harnesses, and rule out the next candidate on the list.
- After the correction, run the system long enough to confirm the skyair fault does not return under normal load.