Full Diagnosis
H7 flags a feedback-signal fault from the outdoor unit fan motor — the control PCB is not receiving the expected rotation/speed signal from an inverter-driven (DC/EC) fan motor, so it disables fan output on that circuit to prevent motor damage or high-pressure buildup from lost airflow. This is a signal/circuit-level fault distinct from E7, which is the broader outdoor fan motor system fault covering physical obstruction, broken harness wiring, or a fan that simply fails to turn regardless of signal integrity.
All Recorded Causes
Broken or shorted fan motor signal (feedback) wire. Loose or corroded connector between fan motor and inverter/control PCB. Defective fan motor speed sensor or Hall element. Faulty inverter PCB fan-drive circuit. Electrical noise interference on the signal line. Fan motor internal winding fault.
Verify Before Replacing Parts
- Confirm the exact Daikin model family and packaged context before acting on a generic code description.
- Confirm board LEDs, wiring polarity, and model compatibility before replacing control boards — this Daikin fault points at broken or shorted fan motor signal (feedback) wire.
- Check for intermittent communication faults caused by connectors, moisture, or damaged harnesses, and rule out loose or corroded connector between fan motor and inverter/control PCB.
- After the correction, run the system long enough to confirm the packaged fault does not return under normal load.