Full Diagnosis
JC is the low-pressure-sensor counterpart to JA: it flags an out-of-range or implausible signal from the suction/low-side pressure transducer that feeds the outdoor PCB for inverter capacity and safety logic, as opposed to the mechanical low-pressure switch (LPS) covered by E4. Because a genuine refrigerant shortage (U0) also drives suction pressure down, JC should be checked alongside actual system charge before condemning the sensor, since a real low-charge condition and a failed sensor can present similarly. The compressor is locked out until a valid low-pressure signal is restored.
All Recorded Causes
Loose, corroded, or swapped connector at the low pressure sensor. High and low pressure sensor connectors reversed. Defective low pressure sensor (transducer). Damaged sensor wiring/harness. Defective outdoor unit PCB analog input circuit. Actual refrigerant shortage or restriction driving suction pressure abnormally low.
Verify Before Replacing Parts
- Confirm the exact Daikin model family and packaged context before acting on a generic code description.
- Confirm board LEDs, wiring polarity, and model compatibility before replacing control boards — this Daikin fault points at loose, corroded, or swapped connector at the low pressure sensor.
- Check for intermittent communication faults caused by connectors, moisture, or damaged harnesses, and rule out high and low pressure sensor connectors reversed.
- After the correction, run the system long enough to confirm the packaged fault does not return under normal load.